BS 5839-1:2025 Clause 24 and Annex E

Power & Batteries

Standby duration, alarm duration, battery-capacity variables and supply fundamentals.

Standby capacity method

Cmin = k × (I₁ × T₁ + I₂ × T₂ × D)

I₁ / T₁
Quiescent current in amperes and the required standby period in hours.
I₂ / T₂
Maximum alarm current in amperes and alarm period in hours.
k
An ageing/temperature allowance selected for the battery and design.
D
Alarm-current derating from manufacturer data or the Annex E method.

The result is minimum new capacity at the stated rate and temperature. Select the next suitable available size and verify manufacturer data.

Open related calculator

Typical Category M/L duty

Standby
At least 24 hours in the usual case; some premises require longer.
Alarm after standby
At least 30 minutes of the required evacuation signal.
Supply arrangement
Normal and standby supplies should each sustain the system’s maximum alarm load.
Source context: BS 5839-1:2025 Clause 24 and Annex E. This page paraphrases the app’s quick-reference material and does not reproduce or replace the standard.