Point detector coverage
- Point smoke detector
- 7.5 m maximum radial distance; about 10.6 m on a square grid.
- Point heat detector
- 5.3 m maximum radial distance; about 7.5 m on a square grid.
- Wall/obstruction clearance
- Keep the sensing position at least 500 mm away where the clause applies.
- Pitched ceiling allowance
- Increase apex coverage by 1% per degree of slope, capped at 25%.
Beams, voids, honeycomb ceilings, high ceilings and air movement require separate assessment.